Master MPS

Power Range: 10 - 200 kVA

3:33:1

Total protection

3:1 10-120 kVA 3:3 10-200 kVA

Master MPS series UPS devices ensure maximum protection and power quality for any type of load, especially for mission critical applications, data centres, security systems and electro-medical equipment, industrial processes and telecommunications. Master Plus is an ON LINE double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with a transformer isolated inverter.

19 models in this range · quoted to order by an authorized Riello UPS reseller

Master MPS

Highlights

  • Efficiency Control System (ECS)
  • Robust and reliable
  • Galvanic isolation
  • High overload capacity
  • Extensive parallel configurations

Models & ordering

Riello model designations are the order codes. Each model is quoted to order; open a model for its full specification and to request pricing and lead time.

ModelRated powerActive powerDimensions (h w d)Weight
MPM 1010000 VA9000 W1400x555x740 mm200 kgQuote
MPM 1515000 VA13500 W1400x555x740 mm220 kgQuote
MPM 2020000 VA18000 W1400x555x740 mm230 kgQuote
MPM 3030000 VA27000 W1400x555x740 mm255 kgQuote
MPM 4040000 VA36000 W1400x555x740 mm302 kgQuote
MPM 6060000 VA54000 W1400x800x740 mm416 kgQuote
MPM 8080000 VA72000 W1400x800x740 mm616 kgQuote
MPM 100100000 VA90000 W1900x800x800 mm665 kgQuote
MPT 1010000 VA9000 W1400x555x740 mm228 kgQuote
MPT 1515000 VA13500 W1400x555x740 mm241 kgQuote
MPT 2020000 VA18000 W1400x555x740 mm256 kgQuote
MPT 3030000 VA27000 W1400x555x740 mm315 kgQuote
MPT 4040000 VA36000 W1400x555x740 mm335 kgQuote
MPT 6060000 VA54000 W1400x800x740 mm460 kgQuote
MPT 8080000 VA72000 W1400x800x740 mm520 kgQuote
MPT 100100000 VA90000 W1900x800x800 mm620 kgQuote
MPT 120120000 VA108000 W1900x800x800 mm640 kgQuote
MPT 160160000 VA144000 W1900x800x800 mm700 kgQuote
MPT 200200000 VA180000 W1900x800x800 mm800 kgQuote

Ships from and sold by A5 IT.

Brochures and data sheets

Select file language
Input
Voltage380 / 400 / 415 V three-phase
Frequency45 - 65 Hz
Frequency tolerance±2% (selectable from ±1% to ±5% from front panel)
Soft start0 - 100% in 120 sec (selectable)
Voltage Range400 V +20% -25%
By Pass
Rated voltage220 / 230/ 240 V single-phase + N
Rated frequency50 or 60 Hz (selectable)
OUTPUT and INVERTER OUTPUT
Rated power10000 VA
Active power9000 W
Output voltage220 / 230 / 240 V single-phase + N (selectable)
Crest factor (Ipeak/Irms)3 : 1
Static stability±1%
Dynamic stability±5% in 10 ms
Frequency50 or 60 Hz (selectable)
Voltage distortion with non-linear load<3%
Voltage distortion with linear load<1%
Frequency stability0.05%
Overload110% for 60 min.; 125% for 10 min.; 150% for 1 min.
Batteries
TypeVRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Environmental
ColorDark grey RAL 7016
CommunicationDouble RS232 + dry contacts + 2 slots for communications interface
Protection ratingIP20
Line-Interactive/Smart Active efficiencyUp to 98%
Noise (at 1 m)60 [dBA±2] (ECO Mode)
Operating temperature0 °C - +40 °C
Relative humidity5-95% non-condensing
StandardsEuropean directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Data
Weight200 kg
Dimensions (h w d)1400x555x740 mm

Characteristics

Easy source

Master MPS makes powering UPS devices by power generators and MV/LV transformers easier and more efficient, reducing loss in systems and coils, correcting the power factor and eliminating harmonics by the loads powered by the UPS itself. In addition to this, the progressive start-up of the rectifier and the possibility of reducing the recharge current of the batteries, allow for the containment of the input current absorbed and therefore do not overload the source, especially when the source is a generator.

Battery Care SYSTEM: maximum battery care

Normally the batteries are kept charged by the rectifier; when mains power fails, the UPS uses this energy source to power its utilities. Therefore, proper battery care is critical to ensuring correct UPS operation in emergency conditions. Battery Care System consists of a series of features and capabilities that allow for battery management in order to obtain the best performance possible and extend their operating life.

Master MPS is also compatible with different battery technologies: vented open lead acid, VRLA AGM, GEL, Ni-Cd, Flywheels, Supercaps and Lithium.

Flexibility

Master MPS is suited to all types of applications, from computers to the most demanding industrial environments. Thanks to the broad range of accessories and options, complex architectures and configurations can be created to ensure maximum power to critical loads: expansions (in redundancy or power) may be made in already-operating parallel systems, even without having to switch off any UPS that are already operating and thus, maintaining power to utilities.

Maximum reliability and availability

Distributed or centralised parallel up to 8 units per redundant (N+1) or powerparallel. A parallel between models with different power levels is possible. Maximum levels of availability also in the event of an interruption to the parallel bus cable: the system is “FAULT TOLERANT”. It is not affected by connection cable faults and continues powering the load without a continuity solution, signalling the anomaly with an alarm.

Options

UGS: UPS Group Synchroniser. Allows 2 or more non-parallel UPS devices to remain synchronised even during mains power failure. The UGS also enables a Riello UPS to be synchronised with another power source that is independent and of a different power rating. PSJ - Parallel Systems Joiner. Allows two groups of UPS to be connected in parallel whilst operating, in the event of maintenance (with no interruption to the output), using a power coupling switch. Should one of the UPS in one of the parallel groups fail, it is automatically excluded. The PSJ connects the remaining UPS, to the other parallel group via an external bypass, in order to continue to guarantee load redundancy.

Specific solutions

The UPS can be adapted to meet your requirements. Contact TEC to discuss the feasibility of specific solutions and options not listed in the catalogue.