Riello UPS

Multi Sentry

Power Range: 160 - 200 kVA

3:3

Exceptional performance and efficiency.

Multi Sentry is a state-of-the-art uninterruptible power supply, achieving the highest possible level of ON LINE double-conversion performance (VFI-SS-111) as defined within IEC EN 62040-3. The UPS has been designed to protect critical information and telecommunications systems, networks, services and processes whose operation could be disrupted by poor power quality and/or breaks in their mains power supply. The sizes available include 160-200 kVA all with a three-phase input and output. The Multi Sentry UPS is one of the most efficient UPS available with a minimal impact on its environment and power sources.

2 models in this range · quoted to order by an authorized Riello UPS reseller

Multi Sentry

Highlights

  • Complete range 160-200 kVA
  • Small footprint
  • High efficiency up to 96.2%
  • Zero impact
  • Flexibility of use
  • Advanced communications

Models & ordering

Riello model designations are the order codes. Each model is quoted to order; open a model for its full specification and to request pricing and lead time.

ModelRated powerActive powerDimensions (h w d)Weight
MST 160160000 VA160000 W1900x840x1035 mm450 kgQuote
MST 200200000 VA200000 W1900x840x1035 mm460 kgQuote

Ships from and sold by A5 IT.

Brochures and data sheets

Select file language
Input
Rated power160000 VA
Voltage380 / 400 / 415 V three-phase + N
Voltage tolerance400 V ±20% @ full load (For wider tolerance conditions apply)
Frequency tolerance40 - 72 Hz
Power factor1
By Pass
Rated voltage380 / 400 / 415 V three-phase + N
Rated frequency50 or 60 Hz (selectable)
Frequency tolerance±5% (selectable)
Number phases3 + N
OUTPUT and INVERTER OUTPUT
Rated power160000 VA
Active power160000 W
Number phases3 + N
Crest factor (Ipeak/Irms)3 : 1
Static stability±1%
Dynamic stability±3%
Frequency50 or 60 Hz
Voltage distortion with non-linear load≤3%
Voltage distortion with linear load≤1%
Batteries
TypeVRLA AGM/GEL/NiCd/Li-ion/Supercaps
Typical recharge time6 h
Environmental
ColorDark grey RAL 7016
Communication3 slots for communications interface / USB / RS232
Protection ratingIP20
Line-Interactive/Smart Active efficiencyUp to 99%
Noise (at 1 m)<50 [dBA±2] (SMART ACTIVE)
Remote signalsvoltage free contacts
Operating temperature0 °C - +40 °C
Relative humidity5-95% non-condensing
StandardsEuropean directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Data
Weight450 kg
Dimensions (h w d)1900x840x1035 mm

Characteristics

ZERO IMPACT SOURCE

Multi Sentry UPS are easy to install, especially on sites where there is limited power capacity available, a standby generator and potentially harmonic compatibility issues:

Multi Sentry also performs the role of a high specification filter, protecting its power supply sources (mains or generator) from any harmonics and reactive power generated by the loads it is powering.

  • low input current distortion - less than 2.5%;
  • high input power factor 0.99;
  • power walk-in function to achieve progressive rectifier start-up;
  • delayed start-up on mains power supply return.

BATTERY CARE SYSTEM

The Multi Sentry Battery Care System optimises battery performance, to help extend their working life and ensure that the UPS can deliver its full-rated back-up time when called upon in an emergency.

Battery recharge: Multi Sentry is designed to work with VRLA AGM and GEL lead-acid batteries including open-vented types, in addition to Ni-Cd. Specific management features include:

Temperature compensation: to avoid excessive voltage being applied to the batteries in a high ambient Battery test: to detect performance degradation and predict battery failure. Deep discharge protection: to prevent the batteries being discharged below a level from which they cannot be recovered (especially when discharged over long periods with very low loads). Low AC ripple current: from a high-frequency battery charger, to ensure the batteries are not subjected to this damaging element commonly experienced with some other UPS and power supply designs. Wide input voltage range: from a rectifier that can work down to less than 40% of its nominal supply rating (at half load), removing the need to discharge the batteries.

  • One-level recharge to meet the requirements of the most common VRLA AGM batteries;
  • Two voltage level recharge meeting the IU characteristic;
  • Restricted charging to reduce electrolyte consumption and extend the life of VRLA batteries.

FLEXIBILITY

Multi Sentry can be used for a wide range of applications, thanks to its configuration options, flexibility, accessories and performance levels:

  • suitable for powering capacitive loads, for example Blade servers - without any reduction in active power, from 0.9 leading to 0.9 lagging;
  • modes of operation include: ON LINE, ECO, SMART ACTIVE and STANDBY OFF;
  • frequency Conversion Mode;
  • Power Share connections for priority-based load shedding when the mains power supply has failed;
  • cold-start facility to switch the UPS on even without a mains power supply present;
  • extensive back-up time options using battery extension cabinets;
  • optional battery cabinet temperature sensor to assist the temperature compensating charger;
  • optional battery chargers to optimize recharge times;
  • optional dual input supplies;
  • optional isolation transformers for Galvanic isolation and neutral connectivity.

ADVANCED COMMUNICATION

Multi Sentry has a large front panel graphic display providing information including: real-time measurements, operating status and alarms conditions - in eight different languages

  • Advanced multi-platform communication, for all operating systems and network environments: PowerShield³ monitoring and shutdown software included with SNMP agent;
  • Compatible with Riello Connect (remote monitoring service);
  • RS232 or USB serial port;
  • Three communication slots for accessories including: network adapters and volt-free contacts;
  • REPO (Remote Emergency Power Off) to shut down the UPS remotely in an emergency;
  • Input for connection of an auxiliary contact for an external manual bypass;
  • Input for synchronisation with an external power source;
  • Graphic mimic panel display for remote connection.

LOW MANAGEMENT COST

The Multi Sentry design provides exceptional performance and efficiency levels, within a very compact footprint and overall case design:

  • High efficiency up to 96% - saving up to 35% in dissipated energy in one year compared to a more traditional UPS (91%) resulting in a faster payback period of four years.
  • High output power factor which at 0.9pF (1pF for models 160-200 kVA) provides up to 15% ( 20% for models 160-200 kVA) more active power compared to a more traditionally sized UPS - providing greater system expansion margin for further load increases.