CSS Sentinel Tower
Power Range: 3 - 5 kVA
The CSS Sentinel Tower by Riello UPS is designed in compliance with standard EN 50171 and is therefore the ideal solution for installation in buildings subject to fire safety regulations and in particular for the power supply of emergency lighting systems. This is not all however, according to local regulations the CSS Sentinel Tower range by Riello UPS is also suitable for supplying power to other emergency systems such as automatic fire extinguishing systems, alarm systems and emergency detection systems, smoke extraction equipment and carbon monoxide detection devices as well as dedicated security systems in sensitive areas. The use of centralised supply systems (CSS) ensures a significant reduction in system set-up and maintenance costs as well as making periodical checks simpler and faster to perform.
2 models in this range · quoted to order by an authorized Riello UPS reseller

Highlights
- Compliance with standard EN 50171
- Protection against battery inversion
- High recharge current
- Continuous overload of 120%
- Casing compliant with standard EN 60598-1
- 10-year life batteries
Models & ordering
Riello model designations are the order codes. Each model is quoted to order; open a model for its full specification and to request pricing and lead time.
| Model | Rated power | Active power | Dimensions (h w d) | Weight | |
|---|---|---|---|---|---|
| CSS CAM 3 | 3000 VA | 3000 W | 500x250x698 mm | 24 kg | Quote |
| CSS CAM 5 | 5000 VA | 5000 W | 500x250x698 mm | 25 kg | Quote |
Ships from and sold by A5 IT.
Press info
Select file language| Input | |
| Voltage | 220 / 230 / 240 V single-phase + N |
|---|---|
| Voltage tolerance | 230 V ±20% at full load (for wider tolerances additional conditions apply) |
| Frequency tolerance | 40 - 72 Hz |
| Power factor | ≥0.99 |
| By Pass | |
| Rated voltage | 220 / 230 / 240 V single-phase + N |
| Voltage tolerance | 180 - 264 V (selectable) |
| Rated frequency | 50 / 60 Hz |
| Frequency tolerance | ±5% (selectable) |
| Number phases | 1 + N |
| OUTPUT and INVERTER OUTPUT | |
| Rated power | 3000 VA |
| Active power | 3000 W |
| Power according with EN 50171 | 2500 VA / W |
| Output voltage | 220 / 230 / 240 V single-phase + N |
| Crest factor (Ipeak/Irms) | 3 : 1 |
| Waveform | Sinusoidal |
| Frequency | 50 / 60 Hz (selectable) |
| Voltage distortion with non-linear load | ≤3% |
| Voltage distortion with linear load | ≤1% |
| Batteries | |
| Type | VRLA - 10 YEARS expected lifespan |
| Built-in battery | No |
| Maximum recharge current | 6 A |
| Environmental | |
| Color | Black RAL 9005 |
| Communication | LCD display / slot for communication interface / USB / REPO / 1 programmable input / 4 output relays |
| Accessories provided | USB cable |
| Surge capability | 1 VDR x 300 J |
| Protections | Overcurrent - short circuit - overvoltage - undervoltage - temperature - excessive low battery |
| Noise (at 1 m) | <48 dBA |
| Operating temperature | 0 °C - +40 °C |
| Relative humidity | 5-95% non-condensing |
| Output sockets | Terminal block + 2 IEC 320 C13 |
| Standards | EN50171 - European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111 |
| Data | |
| Weight | 24 kg |
| Dimensions (h w d) | 500x250x698 mm |
Characteristics
High recharge current and Battery Care System Proper battery care is critical to ensuring correct CSS operation in emergency conditions. The Riello UPS battery care system consists of a series of features and capabilities designed to obtain the best performance, extend operating life and satisfy the recharge times imposed by the standard. The Riello UPS CSS Sentinel Tower range is designed in compliance with standard EN 50171 and ensures high current levels are available for the batteries, allowing recharge of up to 80% of full autonomy within 12 hours. Riello UPS CSS Sentinel Tower are suitable for use with hermetically sealed lead-acid (VRLA), AGM and GEL batteries and Open Vent and Nickel batteries. Different charging methods are available depending on the battery type. The recharge voltage compensation function based on temperature prevents excessive battery charges and overheating. The deep discharge protection prevents reduced battery performance and battery damage.
High overload capacity As required by standard EN 50171, the Riello UPS CSS Sentinel Tower range is designed and sized to support continuous overloads (with no time limits) of up to 120% of nominal load.
Protection against battery inversion Mandatory in line with standard EN 50171, protection against battery inversion ensures the safety of those carrying out maintenance operations on the devices and at the same time prevents damage to the system in the event that the batteries are inadvertently connected with the wrong polarity.
Contact interface All models are equipped with a contact interface configured in compliance with the EN 50171 standard.
General features In addition to the features mentioned here, the Riello UPS CSS Sentinel Tower range has all the features of reliability and flexibility common to the UPS range it derives from, as well as offering compatibility with the main options and accessories.