Key Features
- Frequency Converter 50/400 Hz
- Output voltage: 208 V - 3F
- Galvanic isolation
- Applications: airport, military and naval
- Battery backup
The Riello Master FC400 MFC 125 is part of the Master FC400 (30 - 125 kVA) range — ON LINE UPS. Master FC400 series static Frequency Converters are available from 30 to 125 kVA, with 50 or 60 Hz input and 400 Hz output. The result of extensive experience acquired in the UPS industry, the Master FC400 series is distinguished by the use of technologically advanced components and for excellent reliability, ease of maintenance and ease of operation. The Master FC400 series uses double conversion technology (VFI SS 111 voltage and frequency independent compliant with IEC EN 62040-3), with an integrated output transformer to ensure the galvanic isolation of the load from mains disturbances under all conditions. The output voltage is 208 V threephase (adjustable 200-215 V). Thanks to high frequency IGBT technology and digital control, Master FC400 Frequency Converters are ideal for airport, military and naval applications. The Master FC400 was designed to reduce to a minimum the impact on the mains or generator located upstream, thanks to the low harmonic content input and the progressive start of the rectifier. These features make the Master FC400 frequency converters especially compatible with generators. The Master FC400 requires a small space for installation (only 0.86 m 2 for a 125 kVA model). The main assemblies of the UPS can be easily accessed for maintenance, via the removable front panel. Fans located in the top of the UPS cabinet, eliminate the need for side or rear access, and allow the UPS to be placed against a wall. Master FC400 provides additional protection for a wide range of applications, including: Ships from and sold by A5 IT, an authorized Riello UPS reseller. Quoted to order.
Data
| Weight | 590 kg |
| Dimensions (H W D) | 1900 x 800 x 800 mm |
Input
| Voltage | 380 / 400 / 415 V three-phase |
| Soft Start | 0 - 100% in 120 sec. configurable |
| Voltage Tolerance | 400 V ±20% @ full load |
| Current Distorsion | <5% C (HC Version) |
| Frequency Tolerance | 45 ÷ 65 Hz |
Environmental
| Color | Light gray RAL 7035 |
| Standards | European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111 |
| Communication | Double RS232 + remote contacts + 2 slots for communications interface |
| Noise (At 1 M) | 72 dBA |
| AC/AC Efficiency | up to 92% |
| Protection Rating | IP20 |
| Relative Humidity | 5-95% non-condensing |
| Operating Temperature | 0 °C - 40 °C (50°C @ 75% load) |
OUTPUT And INVERTER OUTPUT
| Overload | 110% for 60 min.; 125% for 10 min.; 150% for 1 min. |
| Waveform | sinusoidal |
| Frequency | 400 Hz |
| Rated Power | 125000 VA |
| Active Power | 100000 W |
| Number Phases | 3 |
| Static Stability | ±1% |
| Dynamic Stability | ±5% |
| Crest Factor (Ipeak/Irms) | 3 : 1 |
| Voltage Distortion With Linear Load | <3% |
| Voltage Distortion With Non-linear Load | <4% |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Frequently Asked Questions
What is the rated power of the Riello Master FC400 MFC 125?▾
Rated power 125000 VA, active power 100000 W.
Which UPS technology does the Master FC400 MFC 125 use?▾
Master FC400 is a ON LINE UPS range (VFI double conversion).
Is the Master FC400 MFC 125 single-phase or three-phase?▾
Phase configuration 3:3 (input:output).
How big is the Master FC400 MFC 125?▾
Dimensions (h × w × d) 1900 x 800 x 800 mm; weight 590 kg.
What communication interfaces does the Master FC400 MFC 125 have?▾
Double RS232 + remote contacts + 2 slots for communications interface.
Can I order the Riello Master FC400 MFC 125 online?▾
This model is quoted to order: request a quote and we come back with pricing and lead time. Ships from and sold by A5 IT, an authorized Riello UPS reseller.