Riello UPS Multi Power2 MP2 300 PCM online double-conversion
Call for Price
Ships from and sold by A5 IT
Call for pricing
This part is quoted to order. Call for current pricing, lead time and volume breaks on the Riello UPS MP2 300 PCM.
224-955-1644Key Features
- Ultra-high efficiency
- Ultimate availability
- Risk-free scalability
- Smart Modular Architecture (SMA)
- Truly sustainable
Data
| Input Phases | 3 |
| Output Phases | 3 |
| Dimensions (H W D) | 1995 x 600 x 940 mm |
| Weight Including PMs To Reach Nominal Power | 429 kg |
Input
| Voltage | 380 / 400 / 415 V three-phase + N |
| Rated Power | 300000 VA |
| Power Factor | 0.99 |
| Frequency Tolerance | 40 - 72 Hz |
By Pass
| Number Phases | 3 + N |
| Rated Voltage | 380 / 400 / 415 V three-phase + N |
| Rated Frequency | 50 or 60 Hz (selectable) |
| Voltage Tolerance | From 180 V (adjustable 180-200) to 264 V (adjustable 250 – 264) referring to neutral (Ph-N) |
| Frequency Tolerance | ± 5% (selectable) |
Batteries
| Type | VRLA AGM / GEL; NiCd; Li-Ion; Supercaps |
| Type Of Charging | One level, Two level, Cyclic recharge (selectable) |
Environmental
| Color | RAL 9005 |
| Standards | European directives: LV 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive & Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111 |
| Communication | 10” Graphic touch screen display – UPS Status led bar – 2 slots for communication interface, 5 input, 4 output signals and embedded NetMan 208 |
| AC/AC Efficiency | Up to 98.1% with MP2 67 PM BLUE (ON LINE mode) |
| Protection Rating | IP20 finger proof (either with cabinet doors open or close) |
| Relative Humidity | 5-95% non condensing |
| Operating Temperature | 0 °C - +40 °C |
Overall Specification
| Parallel (Up To) | 4 |
| Battery Cabinet Type | MP2 300 PCM Power Cabinet |
| Solution Nominal Power | 300 kW |
| Output Power Factor [Pf] | 1 |
| Cabinet Layout Description | Up to 5 x MP2 67 PM BLUE or 5 x MP2 67 PM. Unit with manual bypass switch. |
| Power Module(PM)nominal Power | 67 kW |
OUTPUT And INVERTER OUTPUT
| Overload | 125% for 10 min.; 150% for 1 min. |
| Waveform | Sinewave |
| Frequency | 50 or 60 Hz |
| Rated Power | 300000 VA |
| Active Power | 300000 W |
| Number Phases | 3 + N |
| Output Voltage | 380 / 400 / 415 V three-phase + N |
| Dynamic Stability | EN62040-3 class performance 1 non-linear load |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
What is the rated power of the Riello Multi Power2 MP2 300 PCM?▾
Rated power 300000 VA, active power 300000 W.
Which UPS technology does the Multi Power2 MP2 300 PCM use?▾
Multi Power2 is a ON LINE UPS range (VFI double conversion).
Is the Multi Power2 MP2 300 PCM single-phase or three-phase?▾
Phase configuration 3:3 (input:output).
How big is the Multi Power2 MP2 300 PCM?▾
Dimensions (h × w × d) 1995 x 600 x 940 mm.
What communication interfaces does the Multi Power2 MP2 300 PCM have?▾
10” Graphic touch screen display – UPS Status led bar – 2 slots for communication interface, 5 input, 4 output signals and embedded NetMan 208.
Can I order the Riello Multi Power2 MP2 300 PCM online?▾
This model is quoted to order: request a quote and we come back with pricing and lead time. Ships from and sold by A5 IT, an authorized Riello UPS reseller.