Riello UPS

Sentinel RT 100-240 V 1ph

Power Range: 1000 - 10000 VA

1:1

1000-10000 VA

SENTINEL RT is the high density version of the Premium Pro range of double-conversion ON LINE UPS.

SENTINEL RT is designed to power critical loads such as servers, storage systems, telephone equipment, medical systems and industrial applications.

The UPS is ideal for Blade servers with an input power factor close to Unity (1). The UPS has can be used as tower UPS or within a rackmount cabinet, and takes up only 2U in height. SENTINEL RT has a modern design, choice of functional formats, and represents the state-of-the-art technology from the Riello UPS research & development team. The UPS can achieve an ON LINE operating efficiency of 92%. For critical business continuity applications requiring long runtimes, SENTINEL RT can be installed with battery extension packs. The UPS also incorporates the Riello UPS ‘power-off’ function found in other ECO Line UPS. SENTINEL RT is designed to save energy when no loads are connected.

6 models in this range · quoted to order by an authorized Riello UPS reseller

Sentinel RT 100-240 V 1ph

Highlights

  • Power factor 1 kW = kVA
  • Simplified installation
  • High quality output voltage
  • High battery reliability

Models & ordering

Riello model designations are the order codes. Each model is quoted to order; open a model for its full specification and to request pricing and lead time.

ModelRated powerActive powerDimensions (h w d)Weight
SDH 1000 RT1000 VA1000 W450x87x425/87(2U)x450x425 mm17 kgQuote
SDH 1500 RT1500 VA1500 W450x87x425/87(2U)x450x425 mm18 kgQuote
SDH 2000 RT2000 VA2000 W450x87x625/87(2U)x450x625 mm26.5 kgQuote
SDH 3000 RT3000 VA3000 W450x87x625/87(2U)x450x625 mm31.5 kgQuote
SDH 6000 RT6000 VA6000 W610x87x438 mm17 kgQuote
SDH 10000 RT10000 VA10000 W610x87x438 mm20 kgQuote

Ships from and sold by A5 IT.

Brochures and data sheets

Select file language

Users Guides

Select file language
Input
Rated power1000 V VA
Voltage100-110-115-120-127 V
Voltage tolerance80 V <Vin <150 V @ 100% Load
Frequency60 Hz
Frequency tolerance60 Hz ± 5%
Power factor> 0.98
Current distorsion≤6%
By Pass
Voltage tolerance85 - 140 V
Frequency toleranceFrequency selected (from ±0 Hz to ±5 Hz configurable)
Number phases1
OUTPUT and INVERTER OUTPUT
Rated power1000 VA
Active power1000 W
Number phases1
Crest factor (Ipeak/Irms)3:1
WaveformSinewave
FrequencyCan be selected: 60 Hz or self-learning
Voltage distortion with non-linear load≤4%
Voltage distortion with linear load≤2%
Overload Times
100% < Load < 110%1 minutes
125% = Load < 150%4 seconds
Load > 150%0.5 sec.
Batteries
TypeVRLA AGM lead, maintenance-free
Typical recharge time2-4 h
Environmental
Altitude max6000 m
ColorBlack
CommunicationUSB / DB9 with RS232 and contacts / Slot for communication interface
Safety complianceUL1778:2014 and CSA C22.2 No. 107.3-14
EMC complianceCFR 47 FCC Part 15, Subpart B, Class A 2016
Accessories providedPower cable, serial cable, USB cable, safety manual, quick start, software downloadable
Protection ratingIP20
Surge capability300 joule
MarkscTUVus
Line-Interactive/Smart Active efficiency98%
Noise<40 dB(A) at 3.3 ft / 1 m
Operating temperature32-104 °F / 0-40 °C
Relative humidity<95% without condensation
Data
Weight17 kg
Dimensions (h w d)450x87x425/87(2U)x450x425 mm

Characteristics

Simplified installation

Reduced management costs SENTINEL RT can be programmed remotely via software or set manually from the front mimic panel to operate in a range of energy saving operating modes:

Advanced communications SENTINEL RT offers maximum flexibility for integrations with any communication system.

  • Tower or Rackmount UPS: SENTINEL RT can be installed as tower or 19” rack mount UPS, with a front mimic panel that can be turned through 90º to suit the installation.
  • Noise Free Operation (<40 dBA): the UPS can be installed in any environment thanks to its PWM digitally-controlled high frequency inverter;
  • High Temperature Operation: UPS components are sized for high temperature operation up to 104 °F (40 °C) and are not therefore stressed during normal operational environments.
  • ON LINE: maximum power protection and output voltage waveform quality (efficiency up to 92%);
  • ECO Mode: to increase efficiency (up to to 98%), allows for the selection of LINE INTERACTIVE technology (VI) to power low priority loads from the mains supply;
  • SMART ACTIVE: the UPS automatically decides upon the operating mode (VI or VFI) based on the quality of the mains power supply;
  • STANDBY OFF: the operating mode in which the UPS functions as an emergency device.
  • Multiplatform communication for all operating systems and network environments, Powershield 3 supervision and shut-down software for Windows, Mac OS X operating systems and other Unix operating systems;
  • RS232 serial port and opto-isolated contacts;
  • USB port;
  • Slot for TCP/IP, SNMP communication card.

High quality output voltage

  • Even with non-linear loads (IT loads with a crest factor of up to 3:1);
  • High short circuit current on bypass;
  • High overload capacity: 150% by inverter (even with mains failure);
  • Filtered, stabilised and reliable voltage (TRUE-ON LINE double conversion technology), with filters for the suppression of atmospheric disturbances;
  • Power factor correction: UPS input power factor close to 1 and sinusoidal current uptake.

High levels of battery reliability

  • Automatic and manual battery tests;
  • Batteries are ‘hot-swappable’ and user replaceable.

Other features

  • Output voltage can be selected using display;
  • Auto-restart when mains power returns (programmed via software);
  • Standby on Bypass: when the machine is switched off, it automatically goes into bypass operation with batteries charging;
  • Power-Off with zero load connected to save energy;
  • Low battery warning;
  • Power-on delay;
  • Full microprocessor control;
  • Automatic bypass without interruption;
  • Status, measurements and alarms available on the front panel mimic panel and LCD;
  • UPS firmware upgrade via PC;
  • Input protection including a user reset thermal switch (up to 1500VA);
  • Back-feed protection;
  • Manual option to switch to bypass.

2-YEAR WARRANTY