Sentinel Pro2 208-240 V 1ph
Power Range: 700 - 3000 VA
Input 208-240 V 60 Hz Output 220/240 V 60 Hz
Sentinel Pro2 has a unique, modern design and improved performance created by the Riello UPS research and development team. Sentinel Pro2 uses ON LINE double conversion technology, resulting in the highest levels of reliability and maximum protection for critical loads such as servers, IT and voice/data applications.
For business continuity applications requiring long battery runtimes, battery autonomy can be extended up to several hours using ER models fitted with more powerful battery chargers.
Sentinel Pro2 is supplied as standard with a USB port and an expansion slot for protocol conversion or relay contacts boards. Sentinel Pro2 is available in 700 VA, 1000 VA, 1500 VA, 2200 VA and 3000 VA models.
8 models in this range · quoted to order by an authorized Riello UPS reseller


Highlights
- Power factor 1
- Operating flexibility
- Emergency function
- Battery optimisation
- Runtime expandability
- Low noise level
Models & ordering
Riello model designations are the order codes. Each model is quoted to order; open a model for its full specification and to request pricing and lead time.
| Model | Rated power | Active power | Dimensions (h w d) | Weight | |
|---|---|---|---|---|---|
| SP2 700 A3 | 700 VA | 700 W | 235 x 158 x 422 mm | 10.2 kg | Quote |
| SP2 1000 A3 | 1000 VA | 1000 W | 235 x 158 x 422 mm | 12.5 kg | Quote |
| SP2 1000 ER | 1000 VA | 1000 W | 235 x 158 x 422 mm | 7 kg | Quote |
| SP2 1500 A5 | 1500 VA | 1500 W | 235 x 158 x 422 mm | 13.6 kg | Quote |
| SP2 2200 A3 | 2200 VA | 2200 W | 333 x 190 x 446 mm | 23.3 kg | Quote |
| SP2 2200 ER | 2200 VA | 2200 W | 333 x 190 x 446 mm | 11 kg | Quote |
| SP2 3000 A5 | 3000 VA | 3000 W | 333 x 190 x 446 mm | 26.3 kg | Quote |
| SP2 3000 ER | 3000 VA | 3000 W | 333 x 190 x 446 mm | 11.1 kg | Quote |
Ships from and sold by A5 IT.
Brochures and data sheets
Select file languageUsers Guides
Select file language| Input | |
| Rated power | 700 VA |
|---|---|
| Voltage | 220 / 230 / 240 |
| Voltage tolerance | 230 V ±20% |
| Frequency | 50/60 Hz |
| Frequency tolerance | 50 Hz ±20% / 60 Hz ±20% |
| Power factor | 1 |
| Current distorsion | ≤5.2% |
| By Pass | |
| Voltage tolerance | 180 / 264 V |
| Frequency tolerance | Configurable: 3% ÷ 10% |
| OUTPUT and INVERTER OUTPUT | |
| Rated power | 700 VA |
| Active power | 700 W |
| Number phases | 1 |
| Crest factor (Ipeak/Irms) | 3:1 |
| Waveform | Sinusoidal |
| Frequency | Selectable: 50 or 60 or self-learning |
| Voltage distortion with non-linear load | <4% |
| Voltage distortion with linear load | <2% |
| Overload Times | |
| Load = 150% | 1 s |
| Load = 125% | 4 s |
| Batteries | |
| Type | VRLA AGM maintenance-free lead based |
| Typical recharge time | 2-4 h |
| Environmental | |
| Color | RAL 9005 |
| Communication | USB / RJ45 with dry contacts / Slot for communications interface |
| Safety compliance | IEC EN 62040-1 |
| EMC compliance | EMC 2014/30/EU electromagnetic compatibility; EMC IEC EN 62040-2 |
| Accessories provided | Power cable, IEC-IEC cable, USB cable, safety manual, quick start guide |
| Marks | CE, GS/NEMKO, UL |
| Line-Interactive/Smart Active efficiency | 98% |
| Noise | <40 [dBA] (ECO Mode) |
| Operating temperature | 0 °C - +40 °C |
| Relative humidity | 5-95% non-condensing |
| Standards | European directives: L V 2014/35/EU low voltage; Directive and Standards: RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111; UL 1778:2014 and CSA C22.2 No. 107.3-14 |
| Data | |
| Weight | 10.2 kg |
| Dimensions (h w d) | 235 x 158 x 422 mm |
Characteristics
FEATURES
- Filtered, stabilised and reliable voltage: double conversion ON LINE technology (VFI compliant with IEC 62040-3) with filters for the suppression of atmospheric disturbances;
- High overload capability (up to 150%);
- Programmable Auto-restart when mains is restored;
- Battery start up (Cold Start);
- Wide input voltage tolerance range (from 140 V to 276 V) without battery intervention;
- Runtime extendable up to several hours;
- Fully configurable using UPS Tools configuration software;
- Highly reliable batteries (automatic and manually-activated battery test);
- High level of UPS reliability (total microprocessor control);
- Low impact on the mains (sinusoidal take up).
ADVANCED COMMUNICATION
- Multi-platform communication for all operating systems and network environments: PowerShield 3 supervision and shutdown software for Windows operating systems 10, 8, 7, Hyper-V, 2019, 2016, 2012, and previous versions, Mac OS X, Linux, VMWare ESXi, Citrix XenServer and other Unix operating systems;
- UPS Tools configuration and customisation software supplied as standard;
- Communication port with RJ45 connector and opto isolated contact;
- USB port;